Eaton 003227

t3-6-15168/ea/svb-sw

Stock Limitado solo disponible bajo consulta

Especificaciones

Mounting Position as required
Ancho 65 mm
Peso 362g
ean 4015080032274
product height 74 mm
Product weight .362 kg
catalog notes rated short-time withstand current (icw) for a time of 1 second
10.11 short-circuit rating is the panel builder's responsibility. the specifications for the switchgear must be observed.
rated operational power at ac-3, 380/400 v, 50 hz 11 kw
mounting method flush mounting
Design 15.168
number of switches 1
degree of protection (front side) ip65
short-circuit current rating (high fault) 40 a, class j, max. fuse, sccr (ul/csa)
10 ka, sccr (ul/csa)
rated operational current (ie) at dc-23a, 240 v 5 a
actuator type door coupling rotary drive
ambient operating temperature - max 50 °c
Features version as maintenance-/service switch
version as main switch
rated breaking capacity at 500 v (cos phi to iec 60947-3) 240 a
rated operational power star-delta at 380/400 v, 50 hz 15 kw
10.6 incorporation of switching devices and components does not apply, since the entire switchgear needs to be evaluated.
10.2.6 mechanical impact does not apply, since the entire switchgear needs to be evaluated.
operating frequency 1200 operations/h
number of contacts in series at dc-23a, 48 v 2
terminal capacity 2 x (1 - 6) mm², solid or stranded
14 - 10 awg, solid or flexible with ferrule
1 x (1 - 6) mm², solid or stranded
2 x (0.75 - 4) mm², flexible with ferrules to din 46228
1 x (0.75 - 4) mm², flexible with ferrules to din 46228
heat dissipation capacity pdiss 0 w
assigned motor power at 200/208 v, 60 hz, 1-phase 3 hp
switching angle 90 °
Overvoltage category iii
actuator color black
rated operational current (ie) at dc-13, control switches l/r = 50 ms 20 a
rated operational power at ac-23a, 500 v, 50 hz 15 kw
switching power at 400 v 15 kw
functions stop function
interlockable
rated operational power at ac-3, 690 v, 50 hz 11 kw
10.2.2 corrosion resistance meets the product standard's requirements.
10.2.7 inscriptions meets the product standard's requirements.
rated operational current (ie) star-delta at ac-3, 380/400 v 32 a
number of contacts in series at dc-21a, 240 v 1
Shock resistance 15 g, mechanical, according to iec/en 60068-2-27, half-sinusoidal shock 20 ms
ambient operating temperature (enclosed) - min -25 °c
rated operational current (ie) at dc-21, 240 v 1 a
rated operational current (ie) at ac-23a, 500 v 26.4 a
rated operational power at ac-23a, 220/230 v, 50 hz 7.5 kw
10.2.5 lifting does not apply, since the entire switchgear needs to be evaluated.
rated operational current (ie) at ac-21, 440 v 32 a
10.8 connections for external conductors is the panel builder's responsibility.
assigned motor power at 575/600 v, 60 hz, 3-phase 10 hp
rated operational current (ie) at ac-23a, 690 v 17 a
rated operational power at ac-3, 415 v, 50 hz 11 kw
device construction built-in device fixed built-in technique
static heat dissipation, non-current-dependent pvs 0 w
10.5 protection against electric shock does not apply, since the entire switchgear needs to be evaluated.
Mounting position as required
10.13 mechanical function the device meets the requirements, provided the information in the instruction leaflet (il) is observed.
rated operational power star-delta at 220/230 v, 50 hz 7.5 kw
heat dissipation per pole, current-dependent pvid 1.1 w
switching capacity (auxiliary contacts, general use) 10a, iu, (ul/csa)
uninterrupted current rated uninterrupted current iu is specified for max. cross-section.
assigned motor power at 200/208 v, 60 hz, 3-phase 3 hp
rated breaking capacity at 660/690 v (cos phi to iec 60947-3) 170 a
number of auxiliary contacts (normally closed contacts) 1
rated operational current (ie) star-delta at ac-3, 690 v 25.5 a
rated operational power star-delta at 690 v, 50 hz 22 kw
lifespan, mechanical 500,000 operations
control circuit reliability 1 failure per 100,000 switching operations statistically determined, at 24 v dc, 10 ma)
rated operational voltage (ue) at ac - max 690 v
10.10 temperature rise the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices.
number of contacts in series at dc-23a, 120 v 3
assigned motor power at 230/240 v, 60 hz, 1-phase 3 hp
rated operational current (ie) star-delta at ac-3, 220/230 v 32 a
rated operational current (ie) star-delta at ac-3, 500 v 32 a
product length/depth 162 mm
product width 65 mm
certifications iec/en 60204
csa-c22.2 no. 60947-4-1-14
ul 60947-4-1
iec/en 60947
ul category control no.: nlrv
vde 0660
ul
csa file no.: 012528
csa-c22.2 no. 94
csa
ce
iec/en 60947-3
csa class no.: 3211-05
ul file no.: e36332
rated operational current for specified heat dissipation (in) 32 a
rated operational current (ie) at dc-23a, 24 v 25 a
10.4 clearances and creepage distances meets the product standard's requirements.
rated breaking capacity at 220/230 v (cos phi to iec 60947-3) 260 a
10.2.3.1 verification of thermal stability of enclosures meets the product standard's requirements.
fitted with: black rotary handle and locking ring
short-circuit current rating (basic rating) 5 ka, sccr (ul/csa)
40a, max. fuse, sccr (ul/csa)
rated operational current (ie) at dc-23a, 120 v 12 a
rated conditional short-circuit current (iq) 1 ka
rated making capacity up to 690 v (cos phi to iec/en 60947-3) 320 a
assigned motor power at 115/120 v, 60 hz, 1-phase 1.5 hp
electrical connection type of main circuit screw connection
number of poles 9
ambient operating temperature - min -25 °c
rated uninterrupted current (iu) 32 a
10.3 degree of protection of assemblies does not apply, since the entire switchgear needs to be evaluated.
product category main switch
rated operational current (ie) at dc-23a, 48 v 25 a
number of contacts in series at dc-23a, 24 v 1
assigned motor power at 460/480 v, 60 hz, 3-phase 7.5 hp
rated operational current (ie) at ac-23a, 400 v, 415 v 32 a
10.9.2 power-frequency electric strength is the panel builder's responsibility.
Degree of protection nema 12
rated operational current (ie) at ac-23a, 230 v 32 a
Pollution degree 3
rated impulse withstand voltage (uimp) 6000 v ac
voltage per contact pair in series 60 v
Tightening torque 17.7 lb-in, screw terminals
1.6 nm, screw terminals
rated operational current (ie) at ac-3, 660 v, 690 v 14.7 a
10.2.4 resistance to ultra-violet (uv) radiation uv resistance only in connection with protective shield.
rated operational current (ie) at ac-3, 380 v, 400 v, 415 v 23.7 a
number of auxiliary contacts (normally open contacts) 2
rated operational power at ac-3, 500 v, 50 hz 15 kw
assigned motor power at 230/240 v, 60 hz, 3-phase 3 hp
number of contact units 6
rated operational power at ac-23a, 400 v, 50 hz 15 kw
rated operational current (ie) at dc-23a, 60 v 25 a
10.12 electromagnetic compatibility is the panel builder's responsibility. the specifications for the switchgear must be observed.
ambient operating temperature (enclosed) - max 40 °c
rated operational voltage (ue) at ac - min 690 v
screw size m4, terminal screw
load rating 1.6 x iₑ (with intermittent operation class 12, 40 % duty factor)
2 x iₑ (with intermittent operation class 12, 25 % duty factor)
1.3 x iₑ (with intermittent operation class 12, 60 % duty factor)
rated permanent current at ac-21, 400 v 32 a
climatic proofing damp heat, constant, to iec 60068-2-78
damp heat, cyclic, to iec 60068-2-30
rated breaking capacity at 400/415 v (cos phi to iec 60947-3) 260 a
10.9.3 impulse withstand voltage is the panel builder's responsibility.
safe isolation 440 v ac, between the contacts, according to en 61140
safety parameter (en iso 13849-1) b10d values as per en iso 13849-1, table c.1
rated operational power at ac-23a, 690 v, 50 hz 15 kw
10.9.4 testing of enclosures made of insulating material is the panel builder's responsibility.
rated operational power star-delta at 500 v, 50 hz 18.5 kw
rated operating voltage (ue) - min 690 v
equipment heat dissipation, current-dependent pvid 0 w
suitable for front mounting center
branch circuits, suitable as motor disconnect, (ul/csa)
number of contacts in series at dc-23a, 240 v 5
rated operational current (ie) at dc-1, load-break switches l/r = 1 ms 25 a
10.2.3.2 verification of resistance of insulating materials to normal heat meets the product standard's requirements.
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects meets the product standard's requirements.
number of contacts in series at dc-23a, 60 v 3
rated short-time withstand current (icw) 0.65 ka
650 a, contacts, 1 second
10.7 internal electrical circuits and connections is the panel builder's responsibility.
switching capacity (main contacts, general use) 25 a, rated uninterrupted current max. (ul/csa)
rated operational current (ie) at ac-3, 500 v 23.7 a
rated operational current (ie) at ac-3, 220 v, 230 v, 240 v 23.7 a
short-circuit protection rating 35 a gg/gl, fuse, contacts
switching capacity (auxiliary contacts, pilot duty) a600 (ul/csa)
p600 (ul/csa)
Stock Pedir cotización
Referencia 003227
Fabricante Eaton
Unidades Precio / Unidad
1+ -
  • Registro abierto
    Crea una cuenta en el momento
  • Soporte 24/7
    Pregúntanos a cualquier hora
  • 100% Seguro
    Solo pagos seguros: transferencia bancaria, tarjeta de cédito y PayPal
  • Descuentos por volumen
    Optimice sus suministros