product | dt8p1 : please refer to product catalog/contact csr for more details | ||
product height | 257 mm | ||
Product weight | 35 kg | ||
assigned motor current im at 440 - 480 v, 60 hz, 150% overload | 77 a | ||
rated operational current for specified heat dissipation (in) | 87 a | ||
number of inputs (analog) | 2 (parameterizable, 0 - 10 v dc, 0/4 - 20 ma) | ||
rated operational voltage | 400 v ac, 3-phase 500 v ac, 3-phase 480 v ac, 3-phase |
||
10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
mains voltage - min | 380 v | ||
output frequency - min | 0 hz | ||
system configuration type | ac supply systems with earthed center point | ||
ambient operating temperature at 150% overload - max | 50 °c | ||
ambient operating temperature - max | 50 °c | ||
application in industrial area permitted | no | ||
climatic proofing | < 95 % relative humidity, no condensation, no corrosion, no dripping water | ||
output voltage (u2) | 480 v ac, 3-phase 400 v ac, 3-phase 500 v ac, 3-phase |
||
rated operational power at 380/400 v, 50 hz, 110% overload | 55 kw | ||
static heat dissipation, non-current-dependent pvs | 0 w | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
ambient operating temperature - min | -10 °c | ||
rated control supply voltage | 10 v dc (us, max. 10 ma) | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
electromagnetic compatibility | 1st and 2nd environments (according to en 61800-3) | ||
resolution | 0.01 hz (frequency resolution, setpoint value) | ||
assigned motor power at 460/480 v, 60 hz | 60 hp | ||
assigned motor power at 460/480 v, 60 hz, 110% overload | 75 hp | ||
heat dissipation capacity pdiss | 0 w | ||
number of outputs (analog) | 1 | ||
operating mode | sensorless vector control (slv) u/f control optional: vector control with feedback (clv) |
||
number of outputs (digital) | 1 (parameterizable, 48 v dc/50 ma) | ||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
rated operational current (ie) at 110% overload | 105 a | ||
ambient storage temperature - max | 70 °c | ||
ambient operating temperature at 150% overload - min | -10 °c | ||
assigned motor current im at 400 v, 50 hz, 150% overload | 81 a | ||
converter type | other | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
altitude | above 1000 m with 1 % performance reduction per 100 m max. 3000 m max. 1000 m |
||
industrial valves | dt8p1-10-65-11-in13 |
product length/depth | 640 mm | ||
product width | 237 mm | ||
certifications | certified by ul for use in canada rcm ce dnv iec/en61800-3 ul ul report applies to both us and canada csa class no.: 3211-06 specification for general requirements: iec/en 61800-2 csa-c22.2 no. 14 ul 508c cul rohs, iso 9001 iec/en 61800-3 safety: en 61800-5-1: 2003 iec/en61800-5 ul category control no.: nmms, nmms2, nmms7. nmms8 ul file no.: e134360 |
||
mains voltage - max | 500 v | ||
10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
assigned motor current im at 440/480 v, 60 hz, 110% overload | 96 a | ||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
ambient storage temperature - min | -40 °c | ||
fitted with: | igbt inverter radio interference suppression filter oled display dc link choke internal dc link |
||
rated operational power at 380/400 v, 50 hz | 45 kw | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
protection | finger and back-of-hand proof, protection against direct contact (bgv a3, vbg4) | ||
number of relay outputs | 2 (parameterizable, n/o, 8 a (24 v dc) / 8 a (250 v ac) / 0,4 a (125 v dc)) | ||
communication interface | lonworks, optional modbus-tcp, optional profibus-dp bacnet/ip, optional devicenet, optional canopen®, optional bacnet ms/tp, optional ethercat, optional ethernet ip, optional modbus-rtu, optional profinet, optional |
||
output frequency - max | 320 hz | ||
switching frequency | 3.6 khz, 1 - 10 khz adjustable, fpwm, power section, main circuit | ||
connection to smartwire-dt | no | ||
heat dissipation details | operation (with 150 % overload) | ||
voltage rating - max | 480 vac | ||
number of inputs (digital) | 6 (parameterizable, max. 30 v dc) | ||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
Mounting position | vertical | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
heat dissipation per pole, current-dependent pvid | 0 w | ||
product category | variable frequency drives | ||
radio interference class | c2, c3: depending on the motor cable length, the connected load, and ambient conditions. external radio interference suppression filters (optional) may be necessary. | ||
equipment heat dissipation, current-dependent pvid | 1125 w | ||
rated control voltage (uc) | 24 v dc (external, max. 250 ma) | ||
suitable for | branch circuits, (ul/csa) | ||
rated frequency - min | 45 hz | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
rated operational current (ie) at 150% overload | 87 a | ||
Degree of protection | ip21 nema other |
||
rated frequency - max | 66 hz | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
assigned motor current im at 400 v, 50 hz, 110% overload | 99 a | ||
frame size | fr7 | ||
supply frequency | 50/60 hz | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
application in domestic and commercial area permitted | no | ||
ean | 4015081232789 |