product | dt8p1 : please refer to product catalog/contact csr for more details | ||
product length/depth | 602 mm | ||
product width | 595 mm | ||
certifications | cul iec/en61800-5 ul ul category control no.: nmms, nmms2, nmms7. nmms8 safety: en 61800-5-1: 2003 iec/en 61800-3 ul file no.: e134360 ce certified by ul for use in canada csa class no.: 3211-06 rcm iec/en61800-3 specification for general requirements: iec/en 61800-2 csa-c22.2 no. 14 dnv rohs, iso 9001 ul report applies to both us and canada ul 508c |
||
mains voltage - max | 500 v | ||
10.11 short-circuit rating | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
10.4 clearances and creepage distances | meets the product standard's requirements. | ||
output voltage - max | 500 v | ||
ambient storage temperature - min | -40 °c | ||
fitted with: | control unit dc link choke pc connection radio interference suppression filter internal dc link igbt inverter oled display |
||
ambient operating temperature at 150% overload - max | 50 °c | ||
rated operational power at 380/400 v, 50 hz, 3-phase, 110% overload | 200 kw | ||
output frequency - max | 320 hz | ||
switching frequency | 3.6 khz, 1 - 6 khz adjustable, fpwm, power section, main circuit | ||
ambient operating temperature - min | -10 °c | ||
nominal output current i2n | 385 a | ||
10.3 degree of protection of assemblies | does not apply, since the entire switchgear needs to be evaluated. | ||
product category | variable frequency drives | ||
heat dissipation capacity pdiss | 0 w | ||
assigned motor power at 460/480 v, 60 hz, 3-phase | 250 hp | ||
Protocol | other bus systems tcp/ip devicenet data-highway profibus can lon |
||
Degree of protection | nema 1 ip21 |
||
functions | 4-quadrant operation possible | ||
assigned motor current im at 400 v, 50 hz, 110% overload | 349 a | ||
frame size | fr10 | ||
supply frequency | 50/60 hz | ||
10.2.7 inscriptions | meets the product standard's requirements. | ||
number of inputs (analog) | 2 | ||
assigned motor current im at 440/480 v, 60 hz, 110% overload | 361 a | ||
10.2.5 lifting | does not apply, since the entire switchgear needs to be evaluated. | ||
system configuration type | ac supply systems with earthed center point | ||
protection | finger and back-of-hand proof, protection against direct contact (bgv a3, vbg4) | ||
application in industrial area permitted | yes | ||
connection to smartwire-dt | no | ||
10.9.3 impulse withstand voltage | is the panel builder's responsibility. | ||
number of inputs (digital) | 6 | ||
10.5 protection against electric shock | does not apply, since the entire switchgear needs to be evaluated. | ||
10.13 mechanical function | the device meets the requirements, provided the information in the instruction leaflet (il) is observed. | ||
electromagnetic compatibility | 1st and 2nd environments (according to en 61800-3) | ||
resolution | 0.01 hz (frequency resolution, setpoint value) | ||
equipment heat dissipation, current-dependent pvid | 4000 w | ||
suitable for | branch circuits, (ul/csa) | ||
operating mode | optional: vector control with feedback (clv) u/f control sensorless vector control (slv) |
||
number of outputs (digital) | 1 | ||
10.2.3.3 resist. of insul. mat. to abnormal heat/fire by internal elect. effects | meets the product standard's requirements. | ||
rated operational current (ie) at 110% overload | 385 a | ||
10.7 internal electrical circuits and connections | is the panel builder's responsibility. | ||
relative symmetric net frequency tolerance | 10 % | ||
assigned motor current im at 400 v, 50 hz, 150% overload | 279 a | ||
altitude | max. 1000 m max. 3000 m above 1000 m with 1 % performance reduction per 100 m |
ean | 4015081232819 | ||
product height | 2020 mm | ||
Product weight | 275 kg | ||
assigned motor current im at 440 - 480 v, 60 hz, 150% overload | 302 a | ||
rated operational current for specified heat dissipation (in) | 300 a | ||
rated operational voltage | 500 v ac, 3-phase 480 v ac, 3-phase 400 v ac, 3-phase |
||
output at quadratic load at rated output voltage - max | 200 kw | ||
10.2.3.1 verification of thermal stability of enclosures | meets the product standard's requirements. | ||
mains voltage - min | 380 v | ||
output frequency - min | 0 hz | ||
ambient operating temperature - max | 50 °c | ||
communication interface | bacnet/ip, optional canopen®, optional profibus-dp lonworks, optional devicenet, optional modbus-tcp, optional bacnet ms/tp, optional ethercat, optional ethernet ip, optional modbus-rtu, optional profinet, optional |
||
output voltage (u2) | 500 v ac, 3-phase 400 v ac, 3-phase 480 v ac, 3-phase |
||
heat dissipation details | operation (with 150 % overload) | ||
10.6 incorporation of switching devices and components | does not apply, since the entire switchgear needs to be evaluated. | ||
10.2.6 mechanical impact | does not apply, since the entire switchgear needs to be evaluated. | ||
assigned motor power at 460/480 v, 60 hz, 3-phase, 110 % overload | 300 hp | ||
radio interference class | c2, c3: depending on the motor cable length, the connected load, and ambient conditions. external radio interference suppression filters (optional) may be necessary. | ||
rated control voltage (uc) | 24 v dc (external, max. 250 ma) | ||
rated operational current (ie) at 150% overload | 300 a | ||
10.9.2 power-frequency electric strength | is the panel builder's responsibility. | ||
ambient storage temperature - max | 70 °c | ||
output at linear load at rated output voltage - max | 160 kw | ||
converter type | u converter | ||
10.2.2 corrosion resistance | meets the product standard's requirements. | ||
10.2.4 resistance to ultra-violet (uv) radiation | meets the product standard's requirements. | ||
application in domestic and commercial area permitted | yes | ||
number of phases (output) | 3 | ||
10.12 electromagnetic compatibility | is the panel builder's responsibility. the specifications for the switchgear must be observed. | ||
number of hw-interfaces (rs-485) | 1 | ||
10.8 connections for external conductors | is the panel builder's responsibility. | ||
number of relay outputs | 2 (parameterizable, n/o, 8 a (24 v dc) / 8 a (250 v ac) / 0,4 a (125 v dc)) | ||
climatic proofing | < 95 % relative humidity, no condensation, no corrosion, no dripping water | ||
static heat dissipation, non-current-dependent pvs | 0 w | ||
voltage rating - max | 480 vac | ||
rated control supply voltage | 10 v dc (us, max. 10 ma) | ||
Mounting position | vertical | ||
10.9.4 testing of enclosures made of insulating material | is the panel builder's responsibility. | ||
heat dissipation per pole, current-dependent pvid | 0 w | ||
relative symmetric net voltage tolerance | 10 % | ||
number of outputs (analog) | 1 | ||
rated operational power at 380/400 v, 50 hz, 3-phase | 160 kw | ||
rated frequency - min | 45 hz | ||
10.2.3.2 verification of resistance of insulating materials to normal heat | meets the product standard's requirements. | ||
number of hw-interfaces (other) | 1 | ||
rated frequency - max | 66 hz | ||
ambient operating temperature at 150% overload - min | -10 °c | ||
10.10 temperature rise | the panel builder is responsible for the temperature rise calculation. eaton will provide heat dissipation data for the devices. | ||
number of phases (input) | 3 | ||
industrial valves | dt8p1-06-65-11-in13 |