Dimensions (W x L x H) | (incl. interlinking block and connection technology) 50 x 107 x 70 mm | ||
Number of selectable analogue inputs/outputs | 4 | ||
Parameterisation | Data format Fail-safe per channel Forcing per channel Limit monitoring per channel Idle mode per channel Measured value smoothing Signal range per channel Overflow/underflow monitoring Monitoring according to NE43 inputs Wire break monitoring per channel Number of HART repetitions Wire break per channel Limit value violation as per NE43 per channel Limit value violation per channel HART variables Hysteresis for critical limits Short circuit/overload per channel Parameterisation error Overflow/underflow Behaviour after short circuit/overload | ||
Operator controls | DIL switch | ||
Repetition accuracy | 0.05% at 25ºC | ||
Operational voltage range DC | 18 V ... 30 V | ||
Operating error limit related to the ambient temperature range | ±0.3% | ||
Nominal operating voltage DC | 24 V | ||
Isolation channel - internal bus | yes | ||
CE mark (see declaration of conformity) | To EU EMC Directive | ||
Shock resistance | Shock test with severity level 2 to FN 942017-5 and EN 60068-2-27 | ||
Storage temperature | -20 °C ... 70 °C | ||
Degree of protection | Dependent on the manifold block | ||
Product weight | 77,4 g | ||
Max. input resistance | 300 Ohm | ||
Max. open circuit voltage | 28,8 V | ||
analog input | 0 - 20 mA 4 - 20 mA 4 - 20 mA with HART | ||
Protocol | HART | ||
Sensor type | 0 - 20 mA 4 - 20 mA 4 - 20 mA with HART | ||
Note on materials | RoHS-compliant |
Grid dimension | 50 mm | ||
Diagnosis | Wire break per channel Limit value violation per channel Short circuit/overload per channel Parameterisation error Overflow/underflow Limit value violation as per NE43 per channel | ||
Reverse polarity protection | For all electrical connections | ||
LED display | 1 Group diagnostics 4 channel diagnostics 4 Channel status | ||
Fuse protection (short circuit) | Internal electronic fuse per channel | ||
Intern power consumption nominal operating voltage | Typ. 170 mA | ||
Basic error limit at 25 °C | ±0.1% | ||
Power failure bridging | 10 ms | ||
Isolation channel - channel | no | ||
Vibration resistance | Transport application test with severity level 2 to FN 942017-4 and EN 60068-2-6 | ||
Corrosion resistance class CRC | 1 - Low corrosion stress (when installed) | ||
Relative air humidity | 95 % Non-condensing | ||
Ambient temperature | -5 °C ... 50 °C | ||
Max. load | 750 Ohm | ||
Max. short circuit current | 22 mA | ||
Min. available sensor voltage | 20.7 V at 20 mA | ||
Data format | 15 bits + prefix Scalable to 15 bits | ||
Max. cable length | 500 m | ||
Type of mounting | On interlinking block | ||
Material housing | PA-reinforced PC |
Stock | Pedir cotización |
---|---|
Referencia | 8059847 |
Fabricante | FESTO |
Unidades | Precio / Unidad |
---|---|
1+ | $844,06 |