Dimensions (W x L x H) | (incl. interlinking block and connection technology) 50 x 107 x 50 mm | ||
Diagnosis | Short circuit/overload per channel Undervoltage of outputs | ||
LED display | 1 Group diagnostics 8 channel diagnostics 8 Channel status | ||
Operational voltage range DC | 18 V ... 30 V | ||
Max. power supply per channel | 2.1 A (50 W lamp load), per channel pair | ||
Nominal operating voltage DC | 24 V | ||
Isolation channel - channel | no | ||
Storage temperature | -20 °C ... 70 °C | ||
Ambient temperature | -5 °C ... 50 °C | ||
Characteristic for outputs | Based on IEC1131-T2 | ||
Material housing | PA-reinforced PC |
Number of outputs | 8 | ||
Parameterisation | Fail-safe per channel Forcing per channel Idle mode per channel Behaviour after short circuit Module monitoring | ||
Fuse protection (short circuit) | Internal electronic fuse per channel Additional fuse | ||
Intern power consumption nominal operating voltage | Typ. 34 mA | ||
Max. residual current outputs per module | 8,4 A | ||
Isolation channel - internal bus | Yes, with intermediate air supply | ||
Corrosion resistance class CRC | 1 - Low corrosion stress (when installed) | ||
Degree of protection | Dependent on the manifold block | ||
Product weight | 48 g | ||
Switching logic for outputs | PNP (positive switching) |