Dimensions (W x L x H) | 42.2 x 125.8 x 76.5 mm | ||
Diagnostics via LED | EtherCAT® error EtherCAT® RUN Modify Power supply, electronics/sensors Load power supply System fault Connection status | ||
Configuration support | ESI file | ||
System parameters | Diagnostic memory Fail-safe response Force mode System start | ||
Intrinsic current consumption at nominal operating voltage for electronics/sensors | Typically 64 mA | ||
Nominal DC operating voltage, electronics/sensors | 24 V | ||
Permissible voltage fluctuations for electronics/sensors | ± 25% | ||
Power supply, connection type | Terminal strip | ||
Power supply, number of pins/wires | 4 | ||
Power supply, conductor diameter | 0,2 mm² ... 1,5 mm² | ||
Approval | RCM trademark c UL us listed (OL) | ||
CE mark (see declaration of conformity) | To EU EMC Directive | ||
Vibration resistance | Transport application test with severity level 1 to FN 942017-4 and EN 60068-2-6 | ||
Corrosion resistance class CRC | 0 - No corrosion stress | ||
Relative air humidity | 95 % Non-condensing | ||
Degree of protection | IP20 | ||
Note on ambient temperature | -5 - 60°C for vertical installation | ||
Max. address volume, outputs | 64 Byte | ||
Max. address volume, inputs | 64 Byte | ||
Field bus interface, electrical isolation | yes | ||
Fieldbus interface | EtherCAT® | ||
Field bus, connection type | 2x socket | ||
Field bus, connection pattern | 8 | ||
Fieldbus interface, connection pattern | 995.789 | ||
Fieldbus interface, max. address volume for outputs | 64 Byte | ||
Note on materials | Contains paint-wetting impairment substances RoHS-compliant |
Grid dimension | 18,9 mm | ||
Diagnostics via bus | Wire break Short circuit Parameterisation error Upper limit value violated Overtemperature Lower limit value not observed Undervoltage | ||
Max. number of modules | 10 | ||
Module parameters | Channel alarms bundling Undervoltage diagnostics Channel alarms for undervoltage | ||
Max. power supply | 8 A | ||
Power failure bridging | 20 ms | ||
Power supply, function | Electronics and sensors | ||
power supply, connection system | Spring-loaded terminal | ||
Power supply, connection pattern | 995.847 | ||
Power supply, note on conductor diameter | 0.2 - 2.5 mm² for flexible conductors without wire end sleeves | ||
KC mark | KC-EMV | ||
Certificate issuing authority | UL E239998 | ||
Shock resistance | Shock test with severity level 1 to FN 942017-5 and EN 60068-2-27 | ||
Storage temperature | -20 °C ... 70 °C | ||
Protection against direct and indirect contact | PELV | ||
Ambient temperature | -5 °C ... 50 °C | ||
Product weight | 145 g | ||
Note on outputs | 62 bytes with I/O diagnostic interface 64 bytes with status bits 64 bytes without diagnostics | ||
Note on inputs | 62 bytes with I/O diagnostic interface 63 bytes with status bits 64 bytes without diagnostics | ||
Field bus interface, transmission rate | 100 Mbit/s | ||
Fieldbus interface, function | Bus connection incoming/outgoing | ||
Field bus, connection system | RJ45 | ||
Field bus, protocol | EtherCAT® | ||
Fieldbus interface, max. address volume for inputs | 64 Byte | ||
Type of mounting | With H-rail | ||
Material housing | PA |