Especificaciones
Series (VPPE) | Proportional pressure regulator |
---|---|
Valve function (3) | 3-way valve |
Valve function (1) | Normally closed |
Pneumatic connection (1/8) | Female thread G1/8 |
Pressure regulation range (2) | 0.02 ... 2 bar |
Setpoint input for individual valves (420) | 4 ... 20 mA |
---|---|
Operator unit/interface (E1) | LED display, 7-segment |
Mounting (T) | Common supply manifold mounting (mounting rail) |
Special material properties | None |
Pneumatic connection, port 2 | G1/8 | ||
Total accuracy | 1.5%FS | ||
Electrical connection | 5-pin M12 Plugs | ||
Pneumatic connection, port 1 | G1/8 | ||
Note on materials | RoHS-compliant | ||
Nominal size, supply | 5 mm | ||
Type of actuation | Electric | ||
Mounting position | optional Preferably vertical | ||
Short circuit current rating | For all electrical connections | ||
Symbol | 995.303 | ||
Type of reset | Mechanical spring | ||
Valve function | 3-way proportional pressure regulator | ||
Pressure regulation range | 0,02 bar ... 2 bar | ||
Max. pressure hysteresis | 0,29 psi | ||
Operational voltage range DC | 21,6 V ... 26,4 V | ||
Duty cycle | 100% | ||
Residual ripple | 10 % | ||
Signal range analogue output | 4 - 20 mA | ||
Operating medium | Compressed air to ISO 8573-1:2010 [7:4:4] Inert gases | ||
Approval | RCM trademark c UL us listed (OL) | ||
CE mark (see declaration of conformity) | To EU EMC Directive In accordance with EU RoHS Directive | ||
Certificate issuing authority | UL E322346 | ||
LABS (PWIS) conformity | VDMA24364-B2-L | ||
Degree of protection | IP65 | ||
Product weight | 390 g | ||
Hysteresis | 1 %FS |
Reproducibility | 0,5 %FS | ||
Temperature cooefficient | 0,04 %/K | ||
Type of mounting | With through-hole | ||
Pneumatic connection, port 3 | G1/8 | ||
Material housing | Anodised wrought aluminium alloy | ||
Nominal size, exhaust | 2,5 mm | ||
Sealing principle | Soft | ||
Design | Piloted diaphragm regulator | ||
Safety instructions | Safety position VPPE: if the power supply cable is interrupted, output pressure is maintained unregulated. | ||
Reverse polarity protection | For all electrical connections | ||
Type of piloting | Pilot actuated | ||
Display type | LED indicator 3-digit | ||
Inlet pressure 1 | 0,3 MPa ... 0,4 MPa | ||
Standard nominal flow rate | 310 l/min | ||
Max. current consumption | 160 mA | ||
Max. electrical power consumption | 4,2 W | ||
Switching output | PNP | ||
Signal range analogue input | 4 - 20 mA | ||
Note on operating and pilot medium | Lubricated operation not possible | ||
KC mark | KC-EMV | ||
CE marking (see declaration of conformity) | To UK instructions for EMC To UK RoHS instructions | ||
Corrosion resistance class CRC | 2 - Moderate corrosion stress | ||
Media temperature | 10 °C ... 50 °C | ||
Ambient temperature | 0 °C ... 60 °C | ||
Linearity | 1 %FS |